Honeywell FIre-LITe ALArms MS-9600LS Manual page 189

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the FACP may be used to trip any dialer UL listed for Central
Station/Remote Station Reporting Services.
Note: The Monitor Module input, which is being used to monitor
the 411UD Relay #2 Output (programmed for DACT Trouble),
must be programmed as 'Trouble' at FACP.
Channel 4 (2.2K ELR)
Monitor Module ELR resistor
Relay Output (DACT Trouble)
FACP
Supervisory Relay
FACP
Trouble Relay
24 VDC
nonresettable
power
FACP
Alarm Relay
(2.2K ELRs
P/N 27070)
+ -
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Channel1
Channel 2
Channel 3
1 2 3
1 2 3 4 5 6
FACP
Figure C.2 FACP Connection to 411UD
Alarm
Trouble
Supervisory
Table C.2 411-UD Connections to FACP
NFPA Standard-Specific Requirements
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
411UD
J4 Not Installed
Monitor Module Circuit Input
Monitor Module*
411UD
FACP
TB2-1
TB1-1
TB2-2
TB1-3
TB2-3
TB5-2
TB2-4
TB5-3
TB2-5
TB5-4
TB2-6
TB5-6
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.
SLC Loop
189