Honeywell FIre-LITe ALArms MS-9600LS Manual page 83

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future
Future
Smoke-Conventional
User-Defined-5
Heat-Conventional
User-Defined-6
Medic-Alert
User-Defined-7
Hazard-Alert
User-Defined-8
Tornado-Alert
User-Defined-9
Phone
User-Defined-10
Tamper
User-Defined-11
Supervisory
User-Defined-12
Supervisory-AR
User-Defined-13
HVAC OVRRIDE
Power-Monitor
User-Defined-14
Trouble-Monitor
User-Defined-15
Process-Monitor
User-Defined 16
Process-Monitor-AR
User-Defined-17
Future
Future
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
HVAC RESTART
Drill-Switch-AR
1 Conventional 2-wire smoke detectors may be powered using an external power supply
2 Combination systems employing these non-fire monitor types require the SLC loop to
3 For all entries ending in AR, AR refers to AutoResettable.
4 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
1
2
2
2
3
4
2
2, 3
4
3
Table 3.1 Monitor Types
with an SLC Control Relay Module programmed for Resettable Power operation (refer
to note 1 on page page 89).
be programmed by the installer for Style 4 operation and isolator modules must be
employed on each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC
Wiring Manual (document number 51309). Fire and non-fire devices must not be used
on the same SLC branch.
Operation" on page 198.
Action When Activated
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
Supervisory, latching
same as previous (Medic-Alert)
Supervisory, latching
same as previous (Hazard-Alert)
Supervisory, latching
same as previous (Tornado-Alert)
Active Phone (LCD display only)
same as previous (Phone)
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
Switch Supervisory, nonlatching (tracking)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
Piezo
same as previous (Process-Monitor)
Piezo, nonlatching (tracking)
same as previous (Process-Monitor-AR)
not used
not used
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Switch
Drill Switch, nonlatching (tracking)
Programming
83