Maintenance
Refer back to the appropriate safety warnings.
To return the unit to service after storage, proceed as follows:
1.
Verify that utility power is turned off and that the AUTO/OFF/
MANUAL switch is set to OFF.
2.
Check the tag on the engine for oil viscosity and classification.
Verify that the correct recommended oil is used in the engine
(see the Engine Oil Recommendations section). If necessary,
drain and refill with the proper oil.
3.
Check the state of the battery. Fill all cells of unsealed bat-
teries to the proper level with distilled water. DO NOT USE
TAP WATER IN THE BATTERY. Recharge the battery to 100
percent state of charge, or, if defective, replace the battery.
See "Specifications," for type and size.
4.
Clean and wipe the entire generator.
5.
Make sure the 7.5A fuse is removed from the generator con-
trol panel. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected incorrectly.
6.
Open the fuel shutoff valve.
7.
Insert the 7.5A fuse into the generator control panel. Start the
unit by moving the AUTO/OFF/MANUAL switch to MANUAL.
Allow the unit to warm up thoroughly.
8.
Stop the unit by setting the AUTO/OFF/MANUAL switch to
OFF.
9.
Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
If the battery was dead or disconnected, the exercise timer, cur-
rent date and time must be reset.
24
NOTE:
4.11.3
ACCESSORIES
There are performance enhancing accessories available for the
air-cooled generators.
• Cold Weather Kits are recommended in areas where tempera-
tures regularly fall below 32° F (0° C).
• Scheduled Maintenance Kits include all pieces necessary to
perform maintenance on the generator along with oil recom-
mendations.
• Auxiliary Transfer Switch Lockout enables any of the transfer
switches to completely lock out one large electrical load by
tying into its control system.
• Touch-up Paint Kits are very important to maintain the look and
integrity of the generator enclosure. These kits include touch-up
paint and instructions if the need should arise.
For more details on accessories, please contact a Dealer.