ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
SMART 4 Devices
The mult-criteria sensor SMART 4
logical device type, depending on loop
protocol, is SM4 (CLIP) or SMT4
(OPAL).
or
1
2
3
997-457-000-8, Issue 8
January 2010
5.6.1.2 Sensor Sensitivity Setting
This option allows the sensitivity of sensors to be changed
during device configuration. Access is via the Circuit menu.
Individual sensor Alarm and/or Day settings can be changed.
VIEW
TM
Sensors and SMART 4 Multi-Sensors
The ID60 Panel supports VIEW
Appendix 2, ID60 Single Loop Panel Differences.
Co-operative Multi-sensing Groups
The ID61/62 Panels supports co-operative multi-sensing
through the Advance Warning Addressable Combustion
Sensing (AWACS
devices: VIEW
Sensor), SM3, SM4, (SMART 3 and 4 Multi-criteria
Sensors). Once included in the AWACS
sensitivity configuration follows that for VIEW
i.e. using levels and not a percentage of alarm. During
configuration of the sensor sensitivity values, the LCD returns
to the previously configured value if any of the following occurs:
a. The '
b. The panel state is unchanged for 1 minute.
c. A value outside the predefined operating limits (80% to
120% or L1 to L6 for OPX/SM2, SM3 or SM4) is entered.
To change the sensor sensitivity settings:
1 At the sensor attributes menu, press the '
on the numeric keypad to display the Sensor Sensitivity
Setting menu:
[Sensor nn - AAA]
1 : Alarm(100%)
2 Using the numeric keypad, press '
setting or press '
1
[Sensor nn - AAA]
Enter new alarm level : 120
2
[Sensor nn - AAA]
Enter day mode alarm : 80
3 At the appropriate prompt, use the numeric keypad to
enter the desired percentage value. Press '
confirm the value entered.
[Sensor nn - AAA]
1 : Alarm(120%)
4 Press '
At the appropriate prompt, use the numeric keypad to
enter the desired AWACS group:
[Sensor nn - AAA] Sensitivity
Enter new AWACS Group : _
5 Press '
press '
68
TM
) software algorithm for the following
TM
, ION, OPT, MLT, OPX/SM2 (Optiplex Multi-
TM
' button on the numeric keypad is pressed.
4
Sensitivity
2 : Day(100%) 3 : Group (00)
' to select the Alarm Sensitivity
1
' to select the Day Mode Sensitivity setting.
2
Sensitivity
Sensitivity
Sensitivity
2 : Day(80%)
' to select a new AWACS group, if required.
3
' to confirm the AWACS group entered or
5
' to cancel.
4
and SMART 4. See
TM
algorithm, the
TM
device types,
' button
3
< : Cancel
< : Cancel
' to
5
< : Cancel
< : Cancel