Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 49

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
or
2
8
6
3
or
2
8
6
5
4
2 Press the '
/
2
8
Options until the Pulse On/Off Ratio screen is displayed.
[Setup]
Pulse On/Off ratio = 1/1
> : Change
3 Press the '
' button to change the required setting
6
to either 1/1 or 4/1.
[Setup]
Pulse On/Off ratio = 4/1
> : Change
4 Press '
' to return to the Setup menu screen.
4
5.5.3.3 Auto High Test
The Auto High Test setup menu configures the panel to
test each device on the loop at a specified time. The test
checks that each device is able to produce an alarm
reading at the panel. To configure the Auto High Test:
1 From the Setup menu screen, using the numeric keypad
press the '
' button to enter the Device Options menu.
3
[Setup]
Device Blinking = ON
> : Change
2 Press the '
/
2
8
Options until the Auto High Test screen is displayed.
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
3 Press the '
' button to enter (edit) the time at which
6
Auto High Test will start.
[Setup]
Auto High Test = DISABLED
Enter start time :
-0:00
4 Using the numeric keypad, enter an appropriate start
time in the 24-hour clock format and confirm the set
time using the '
5
to the Auto High Test screen. Alternatively, press '
cancel all changes and return to the Auto High Test screen.
[Setup]
Auto High Test = 07:46
> : Change
1 : Disable
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
45
' buttons to step through the Device
: More
< : Exit
: More
< : Exit
: More
< : Exit
' buttons to step through the Device
: More
< : Exit
< : Cancel
' button. The LCD automatically returns
: More
: More
997-457-000-8, Issue 8
January 2010
' to
4
< : Exit
< : Exit