ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
997-457-000-8, Issue 8
January 2010
SENSOR AT ADDRESS ZERO - A sensor has been
installed without setting a valid address, i.e. left at factory
default of '00'. Action: Change to valid address.
MODULE AT ADDRESS ZERO - A module has been
installed without setting a valid address, i.e. left at factory
default of '00'. Action: Change to valid address.
SENSOR AT ADDRESS OUT-OF-RANGE - a sensor has
its address set to greater than 99 (new OPAL protocol
devices only).
MODULE AT ADDRESS OUT-OF-RANGE - a module
has its address set to greater than 99 (new OPAL protocol
devices only).
SIGNAL DEGRADED - Data returned from a device is
being corrupted. Action: Check the continuity of the loop
screen and that the screen is only earthed at one point.
ISOLATOR OPEN - loop isolator is open circuit either by
command from the panel or because of a loop fault.
LOOP SUPERVISION FAULT - there is a problem with a
loop device that has a fault monitored circuit such as a
conventional detection zone. Action: Check the zone
wiring for open- or short-circuit faults.
INCORRECT DEVICE PROTOCOL - an OPAL protocol
device has been replaced with a CLIP. Action: Either fit
the correct protocol device type or re-learn the device at
that address as a CLIP - providing the total of 10 CLIP
devices on the loop is not exceeded.
Power Supply Faults
PSU BOOSTER OVERVOLTAGE - The boosted output
voltage from the PSU is too high. Action: Replace base
board.
PSU I/O CONNECTION FAULT - There is a wiring
connection problem between the PSU and the base PCB
or the battery charger has blown. Action: Check PSU
connections/charger fuse.
MAINS/PSU FAULT - The mains input supply has
dropped to an unacceptable level or the PSU has
developed a fault. Action: Check mains supply. If mains
supply OK, replace PSU.
MAINS SUPPLY LOW - The mains supply voltage is
unusually low. Action: check mains voltage.
BATTERY CHARGER FAILURE - The integral battery
charger has failed and the batteries are no longer being
charged. Action - replace base board.
BATTERY LOW - The battery voltage is unusually low.
Action - Check the batteries and, if necessary, replace
them with new batteries.