Honeywell NOTIFIER AM-8000 Programming Manual page 56

Intelligent addressable fire detection
Hide thumbs Also See for NOTIFIER AM-8000:
Table of Contents

Advertisement

The "SEDEL" operator is equal to the "DEL" operator, with the difference that, if during the delay time the
equation is not true any longer, the timer continues to count and then it activates the output device.
To re-set this timer perform an alarm or Fault reset.
is the operator that allows to program output activations at periodic time intervals.
There can be two formats :
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA
Where : 00 = hours, MM = minutes
This format allows to perform programmings weekly, for specific days of the week
FORMAT Type 2 : TIM (MM GG AA
Where : MM = month, GG = day, AA =year
This format allows to perform programmings yearly
Example: IF the G90 software group equation is : TIM (SA SU 07.30 13.59)
THEN the G90 group will be active on Saturday and Sunday from 07.30 a.m. to 13.59.
N.B.:
If the day, month or year is not specified, the value assumes the meaning of "All days".
To not specify anything enter two signs "  " refer to the following example:
The start time and end time values, use the 24 hour format (midnight = 00.00 ... 23.59)
The value "00.MM" of end time MUST be higher than the value of the start time.
The maximum value for start time and end time is 23:59
Pag. 52
NOTIFIER ITALIA
activation days
(optional)
Enter a space
character
Activation date
(optional)
TIM (   07.30 13.59)
Doc. M-160.2-AM-8000-ENG Rev A1
SDEL
TIM
Enter a
Enter a
space character
space character
00.MM
start time
Enter a space
character
OO.MM
OO.MM)
start time
end time
Programming Manual
00.MM)
end time
AM8000_manu-prog-ENG
SERIEAM

Advertisement

Table of Contents
loading

Table of Contents