For UDS panels two specific Type ID are reserved, UDS1 and UDS2.
UDS units can be installed from the tenth starting address with the exclusion of the decade from 0 to 9, and
occupy from a minimum of 2 to a maximum of 6 addresses.
The basic installation, compatible with UDS-1N type units ( now obsolete ) , occupies the first two addresses to
which the type-ID UDS1 is assigned; the operation is allowed only on the first address but is automatically
extended to the second address.
In the subsequent four addresses the optional modules which have been introduced with the UDS-2N and the
present UDS-3N unit can be installed; to perform this operation just insert the type-ID = UDS2.
For a detailed description of the functionalities associated with the interface modules with UDS units consult the
relevant manuals.
For UDS modules, the following specific indications are obtained:
Address
1st address (X0)*
2nd address (X1)*
3rd address (X2)*
4th address (X3)*
5th address (X4)*
6th address (X5)*
N.B. :
* X can have the values from 1 to 9
UDS unit removal
The UDS unit is completely removed (including the optional UDS2 modules possibly installed) by re-setting the
type-ID NONE on the first address.
This is also the only system to remove the type-ID UDS 1; UDS2 type modules can be also removed one by
one.
Fault event signals from UDS panels connected to the AM-8000 control unit
Key selector on UDS-3N in "Manual" or "Disabled" position in AM-8000 control unit; there will be the
following signallings:
Yellow led "Exclusions" lit.
The symbol
In the system exclusion list display there is the indication " Excl UDS Addr XX" where XX is
the first address assigned to the UDS-3N panel.
General Fault on the UDS-3N panel in AM-8000 control unit; there will be the following signallings:
Yellow led "FAULTS" flashing
The symbol
The display shows the indication "UDS XX GEN" where XX is the third address (with
description "GEN_FAULT") assigned to the UDS-3N panel.
In case of Anomaly on the extinguishing line of UDS-3N panel in AM-8000 control unit; there will be
the following signaling:
Yellow led "FAULTS" flashing
The symbol
The display shows the indication "US XX : Fault EXTING" where XX is the fourth address (with
description "EXT_ FAULT") assigned to the UDS-2N panel.
In case of no 230 Vac power supply on the USD-3N panel in AM4000 control unit there are the
following signaling:
Yellow led "FAULTS" flashing
The symbol
The display shows two indications:
"UDS XX : GEN FAULT" where XX is the third address (description "GEN_FAULT").
"UDS XX : POWER FAULT." where XX is the sixth address (description "POW_FAULT" )
Pag. 28
NOTIFIER ITALIA
o
r
U
D
S
u
n
i
t
s
o
r
U
D
S
u
n
i
t
s
Type ID
Description and signallings
UDS1 "ALL1"
UDS1
"ALL2"
UDS2
"GEN_FAULT" (General fault on UDS-2N)
UDS2
"EXT_FAULT" (Anomaly on the extinguishing line of the UDS-2N panel)
UDS2 "AUT_DIS" (disabling of the UDS-2N panel)
UDS2 "POW_FAULT" (Fault for no 230 Vac power supply on UDS-2N panel)
" ! "
is on the control unit state icon.
"  "
on the control unit state icon.
"  "
is on the control unit state icon.
"  "
is on the control unit state icon.
Doc. M-160.2-AM-8000-ENG Rev A1
Programming Manual
SERIEAM
AM8000_manu-prog-ENG