Examples of programming:
OPTIONS
The following example points out three ways to perform a simple programming, that is the output module
activation as a response to an alarm on a detector (or any other alarm input device)
OPTION A
Fire detection device
LOOP 1 - detector 1
Output device
LOOP 1 – output module 1
Detector equation = (G1)
Module equation = (G1)
GENERAL ALARM
The following example shows a method of control unit programming for the general alarm.
Fire detection
device L1S1
Software
group
1
Output device
L1M2
The L1M2 output module is associated with the group G1 and will be activated in case of alarm on the L1S1
and L1S2 detectors.
The L1M3 output module is associated with the group G2 and will be activated in case of alarm on the L1S3
detectors or on the L1M1 input module.
The L1M4 output module is used as a general alarm device; it will be activated in case of alarm on any fire
detection device (detector or input module) of the system, because all fire detection devices are associated with
the group G3.
AM_8000
AM8000_manu-prog-ENG
OPTION B
Fire detection device
LOOP 1 – detector 1
Output device
LOOP 1 – output module 1
Detector equation =
Module equation = (L1S1)
Fire detection
device L1S2"
Software
group 2
Output device
L1M3
Programming Manual
Doc. M-160.2-AM-8000-ENG Rev A1
Fire detection device
LOOP 1 - detector 1
Output device
LOOP 1 – output module 1
Detector equation = (L1M1)
Module equation =
Fire detection
device L1S3
Software
group
3
Output device
L1M4
OPTION C
Fire detection
device L1M1
PAGINA - 53
NOTIFIER ITALIA