SCS Series Manual — P/N 15712:L 7/18/16
When used with an SCE, eight switch groups are
available for group type 14 operation and eight are
14 14
available for group type 4 operation in the format
4
4
shown to the left. Type 14 switch groups require two
4
4
control modules and one monitor module. Type 14
14 14
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 4 switch groups require one control module. Type 4 switch groups can
SCE-8
be used for fans or dampers. The control module is used for OFF control of a fan.
When used with an SCE, eight switch groups are
available for group type 12 operation and eight are
12
5
available for group type 5 operation in the format
12
5
shown to the left. Type 12 switch groups require two
12
5
control modules. Type 12 switch groups are usually
12
5
only used for fans. One control module is used for OFF control of a fan and the other is used for ON
control of the fan. Type 5 switch groups require one control module and one monitor module. Type
5 switch groups can be used for fans or dampers. The control module is used for OFF control of a
SCE-8
fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 12 operation and eight are
12
6
available for group type 6 operation in the format
12
6
shown to the left. Type 12 switch groups require two
12
6
control modules. Type 12 switch groups are usually
12
6
only used for fans. One control module is used for OFF control of a fan and the other is used for ON
control of the fan. Type 6 switch groups require one control module and one monitor module. Type
6 switch groups can be used for fans or dampers. The control module is used for OFF control of a
SCE-8
fan and the monitor module is used for the ON verification of the fan.
When used with an SCE, eight switch groups are
available for group type 12 operation and eight are
12
7
available for group type 7 operation in the format
12
7
shown to the left. Type 12 switch groups require two
12
7
control modules. Type 12 switch groups are usually
12
7
only used for fans. One control module is used for OFF control of a fan and the other is used for ON
control of the fan. Type 7 switch groups require one control module and two monitor modules. Type
7 switch groups are usually only used for dampers. The control module is used for CLOSED control
SCE-8
of a damper, one monitor module is used for the OPEN verification of the damper and the other
monitor module is used for the CLOSED verification of the damper.
When used with an SCE, eight switch groups are
available for group type 13 operation and eight are
13
5
available for group type 5 operation in the format
13
5
shown to the left. Type 13 switch groups require two
13
5
control modules and one monitor module. Type 13
13
5
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the OFF
verification of the fan. Type 5 switch groups require one control module and one monitor module.
SCE-8
Type 5 switch groups can be used for fans or dampers. The control module is used for OFF control
of a fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 13 operation and eight are
13
6
available for group type 6 operation in the format
13
6
shown to the left. Type 13 switch groups require two
13
6
control modules and one monitor module. Type 13
13
6
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the OFF
verification of the fan. Type 6 switch groups require one control module and one monitor module.
SCE-8
Type 6 switch groups can be used for fans or dampers. The control module is used for OFF control
of a fan and the monitor module is used for the ON verification of the fan.