Honeywell NOTIFIER SCS Series Operation And Installation Manual page 131

Smoke and hvac control station
Table of Contents

Advertisement

Non-dedicated Smoke Control System Wiring Diagrams
Power Source
1a listed
contactor
1b listed
contactor
Service
Disconnect
Switch
Figure 5.22 depicts a fan in a non-dedicated system with the capability of
type 8. In the above configuration, the CON
always in the opposite state when the smoke control system is in operation and are always deactivated during normal operation. The
CON
CM is wired in parallel with the EMS; when wired in parallel with the EMS the CM must be a relay module. When the
ON⁄OP
CON
CM and the CON
ON⁄OP
supplied to the fan. When no power is supplied to the fan, the fan is
VER
MM monitors the
ON⁄OP
deactivated because the fan is
whatever state the EMS is in and closes the normally open contactor, thus supplying power to the fan and turning it
CON
CM is activated for smoke control, the CON
OFF⁄CL
whatever state the EMS is in.
Switch group type 9 is used for
verification from switch group type 7 or switch group type 8, switch group type 9 would only be necessary for redundancy in verifying the
state of the fan. For example, if switch group type 7 is used instead of switch group type 8, the
the monitor module is activated and the
types 7 or 8 also saves the use of an additional monitor module. Switch group type 9 would use two monitor modules to provide the same
verification as types 7 or 8.
SCS Series Manual — P/N 15712:L 7/18/16
Energy
Management
System
CON
CM
ON/OP
(deactivated)
FRM-1
(use 3.9K listed ELR with FZM-1)
FAN OFF
Power Return
Figure 5.22 Fan Control, Non-dedicated System - FSCS Switch Group Type 8
CM is deactivated and the CON
ON⁄OP
CM are deactivated, the EMS is free to control the fan. In this case the EMS is
OFF⁄CL
position of the sail switch, which would indicate when the fan is
OPEN
due to the EMS. When the CON
OFF
and
control and verification of the
ON
OFF
state of the fan would be verified when the monitor module is deactivated. Utilizing switch group
ON
Listed
24 VDC
Power Source
Listed
24 VDC
Power Source
ELR-47K
Listed
Sail
Switch
N/O
COM
N/C
and
ON
OFF
OFF⁄CL
and the sail switch is
OFF
CM is activated for smoke control, the CON
ON⁄OP
CM opens the normally closed contactor and turns the fan
OFF⁄CL
and
state. Since it is possible to determine both
ON
OFF
Ratings and Wiring Diagrams
CON
CM
OFF/CL
(deactivated)
*If the SLC device
does not match the
one in this figure, refer
to the SLC manual
appendix, which
contains wiring
conversion charts for
type V and type H
FCM-1
modules.
VER
MM
OFF/CL
(deactivated)
FMM-1
SLC Loop
control and verification of the
CM is deactivated. These two control modules are
OFF
, indicating no airflow in the duct. The
CLOSED
. In this case the VER
ON
state of the fan would be verified when
OFF
state, switch group
ON
, so no power is being
MM is
ON⁄OP
CM overrides
ON⁄OP
. When the
ON
, overriding
OFF
and
ON
OFF
131