SCS Series Manual — P/N 15712:L 7/18/16
When used with an SCE, all 16 switch groups are
available for group type 14 operation. Type 14 switch
14 14
groups require two control modules and one monitor
14 14
module. Type 14 switch groups are usually only used
14 14
for fans. One control module is used for OFF control
14 14
of a fan and the other is used for ON control of the fan. The monitor module is used for the ON
verification of the fan.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 15 operation. Type 15 switch
15 15
groups require two control module and two monitor
15 15
modules. Type 15 switch groups are usually only
15 15
used when redundancy of fan verification or damper
15 15
control is necessary. One control module is used for OFF control of a fan and the other is used for
ON control of the fan. One monitor module is used for the OFF verification of the fan and the other
is used for ON verification of the fan.
SCE-8
When used with an SCE, eight switch groups are
available for group type 13 operation and eight are
13
7
available for group type 7 operation in the format
13
7
shown to the left. Type 13 switch groups require two
13
7
control modules and one monitor module. Type 13
13
7
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the OFF
verification of the fan. Type 7 switch groups require one control module and two monitor modules.
SCE-8
Type 7 switch groups are usually only used for dampers. The control module is used for CLOSED
control of a damper, one monitor module is used for the OPEN verification of the damper and the
other monitor module is used for the CLOSED verification of the damper.
When used with an SCE, eight switch groups are
available for group type 14 operation and eight are
14
5
available for group type 5 operation in the format
14
5
shown to the left. Type 14 switch groups require two
14
5
control modules and one monitor module. Type 14
14
5
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 5 switch groups require one control module and one monitor module.
SCE-8
Type 5 switch groups can be used for fans or dampers. The control module is used for OFF control
of a fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 14 operation and eight are
14 14
available for group type 5 operation in the format
5
5
shown to the left. Type 14 switch groups require two
5
5
control modules and one monitor module. Type 14
14 14
switch groups are usually only used for fans. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 5 switch groups require one control module and one monitor module.
SCE-8
Type 5 switch groups can be used for fans or dampers. The control module is used for OFF control
of a fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 14 operation and eight are
14
6
available for group type 6 operation in the format
14
6
shown to the left. Type 14 switch groups require two
14
6
control modules and one monitor module. Type 14
14
6
switch groups are usually only used for fans. One control module is used for ON control of the fan,
the other control module is used for the OFF control. The monitor module is used for ON
verification of the fan. Type 6 switch groups require one control module and one monitor module.
SCE-8
Type 6 switch groups can be used for fans or dampers. The control module is used for OFF control
of a fan and the monitor module is used for the ON verification of the fan.
Table 3.10 HVAC Mode Dipswitch Settings (3 of 5)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
The SCS⁄SCE