Non-dedicated Smoke Control System Wiring Diagrams
Power Source
Listed contactor
for Energy
Management
System
1b listed
contactor
Service
Disconnect
Switch
Figure 5.18 depicts a fan in a non-dedicated system with the capability of
the above configuration, the CON
to the fan (the contactor is used when the power being switched is greater than 24 volts). When the CON
tactor is closed, thus allowing the EMS to freely control the fan. In this case the EMS is
no power is supplied to the fan, the fan is
the
position of the sail switch, which would indicate when the fan is
OPEN
is
due to the EMS. When the CON
OFF
was being supplied by the EMS.
Switch group type 3 is for a fan that would require the capability of
sible to determine this information from either switch group type 1 or switch group type 2, switch group type 3 would only be necessary for
redundancy in verifying the state of the fan. For example, if switch group type 1 is used instead of switch group type 3, the
fan would be verified when the monitor module is activated and the
tivated. Utilizing switch group types 1 or 2 also saves the use of an additional monitor module. Switch group type 3 would use two monitor
modules to provide the same verification as types 1 or 2.
SCS Series Manual — P/N 15712:L 7/18/16
Energy Management System
(use 3.9K listed ELR with FZM-1)
FAN OFF
Power Return
Figure 5.18 Fan Control, Non-dedicated System - FSCS Switch Group Type 2
CM is deactivated. The CON
OFF⁄CL
and the sail switch is
OFF
CM is activated, the normally closed contactor opens, thus cutting any power to the fan that
OFF⁄CL
Listed
24 VDC
Power Source
Listed
24 VDC
Power Source
ELR-47K
Listed
Sail
Switch
N/O
COM
N/C
control and verification of the
OFF
CM controls a normally closed contactor which switches power
OFF⁄CL
, so no power is being supplied to the fan. When
OFF
, indicating no airflow in the duct. The VER
CLOSED
. In this case the VER
ON
control and verification of both the
OFF
state of the fan would be verified when the monitor module is deac-
ON
Ratings and Wiring Diagrams
CON
CM
OFF/CL
(deactivated)
*If the SLC device does
not match the one in
this figure, refer to the
FCM-1
SLC manual appendix,
which contains wiring
VER
MM
ON/OP
conversion charts for
(deactivated)
type V and type H
modules.
FMM-1
SLC Loop
state, switch group type 2. In
ON
CM is deactivated, the con-
OFF⁄CL
MM monitors
ON⁄OP
MM is deactivated because the fan
ON⁄OP
and
states. Since it is pos-
ON
OFF
OFF
state of the