Honeywell NOTIFIER SCS Series Operation And Installation Manual page 68

Smoke and hvac control station
Table of Contents

Advertisement

The SCS⁄SCE
8
7
7
7
7
7
7
7
7
SCS-8
9
8
8
8
8
8
8
8
8
SCS-8
10
9
9
9
9
9
9
9
9
SCS-8
11
10 10
10 10
10 10
10 10
SCS-8
12
11 11
11 11
11 11
11 11
SCS-8
13
12 12
12 12
12 12
12 12
SCS-8
14
13 13
13 13
13 13
13 13
SCS-8
68
When used with an SCE, all 16 switch groups are
available for group type 7 operation. Type 7 switch
7
7
groups require one control module and two monitor
7
7
modules. Type 7 switch groups are usually only used
7
7
for dampers. The control module is used for CLOSED
7
7
control of a damper, one monitor module is used for the OPEN verification of the damper and the
other monitor module is used for the CLOSED verification of the damper.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 8 operation. Type 8 switch
8
8
groups require one control module. Type 8 switch
8
8
groups can be used for fans or dampers. The control
8
8
module is used for ON control of a fan.
8
8
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 9 operation. Type 9 switch
9
9
groups require one control module and one monitor
9
9
module. Type 9 switch groups can be used for fans or
9
9
dampers. The control module is used for ON control
9
9
of a fan and the monitor module is used for the OFF verification of the fan.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 10 operation. Type 10 switch
10 10
groups require one control module and one monitor
10 10
module. Type 10 switch groups can be used for fans
10 10
or dampers. The control module is used for ON
10 10
control of a fan and the monitor module is used for the ON verification of the fan.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 11 operation. Type 11 switch
11 11
groups require one control module and two monitor
11 11
modules. Type 11 switch groups are usually only
11 11
used for dampers. The control module is used for
11 11
OPEN control of a damper, one monitor module is used for the OPEN verification of the damper
and the other monitor module is used for the CLOSED verification of the damper.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 12 operation. Type 12 switch
12 12
groups require two control modules. Type 12 switch
12 12
groups are usually only used for fans. One control
12 12
module is used for OFF control of a fan and the other
12 12
is used for ON control of the fan.
SCE-8
When used with an SCE, all 16 switch groups are
available for group type 13 operation. Type 13 switch
13 13
groups require two control modules and one monitor
13 13
module. Type 13 switch groups are usually only used
13 13
for fans. One control module is used for OFF control
13 13
of a fan and the other is used for ON control of the fan. The monitor module is used for the OFF
verification of the fan.
SCE-8
Table 3.10 HVAC Mode Dipswitch Settings (2 of 5)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
SCS Series Manual — P/N 15712:L 7/18/16