Multiple Smoke Control Station
See NCA-2 Manual for instructions on programming the following example.
ZL498 = OR(SCSDIS(A25),N2ZL498)
ZL499 = OR(AUTO(A25))
ZL500 = AND(NOT(SCSDIS(A25)),NOT(N2ZL500))
ZL501 = AND(ZL499,N2ZL499)
N2ZL500
Figure C.1 Programming Example 1: Primary Panel, Normally in Control, Enabled
SCS Series Manual — P/N 15712:L 7/18/16
NCA-2 (N1)
Primary MSCS Panel
Programming
Custom Graphics
Annunciator
SCS-8L
LDM-32
(A25)
Visual
Indicators
Primary SCS
ZL498 will be active when the primary's
Disabled
enable/disable switch is disabled and the secondary
NCA-2 SCS is enabled/disabled.
--
Required for Multiple Smoke Control Systems
applications; monitors the Auto status of the SCS-
8L (designated as A25 in this example).
Logic zone address must be lower than that of the
MSCS Control Zone.
Primary SCS
ZL500 identifies the MSCS Control Zone of the
Active
primary NCA-2. This logic zone will be active when
the primary's enable/disable switch (SCSDIS) is
enabled and the secondary NCA-2 is disabled.
--
Required to track when the SCS-8L is in Auto. SCS-
8L must use the next consecutive logic zone
address after the MSCS Control Zone of the primary
NCA-2.
Secondary SCS
N2ZL500 identifies the MSCS Control Zone of the
Active
secondary NCA-2.
Special Applications
User interface for
Primary MSCS:
• Enable/Disable switch
• Control switches
• Visual indicators
Notes