Honeywell NOTIFIER SCS Series Operation And Installation Manual page 58

Smoke and hvac control station
Table of Contents

Advertisement

The SCS⁄SCE
17
5
5
3
3
3
3
5
5
SCS-8
18
8
1
8
1
8
1
8
1
SCS-8
19
8
8
1
1
1
1
8
8
SCS-8
20
8
2
8
2
8
2
8
2
SCS-8
21
8
8
2
2
2
2
8
8
SCS-8
22
8
3
8
3
8
3
8
3
SCS-8
58
When used with an SCE, eight switch groups are
available for group type 5 operation and eight are
5
5
available for group type 3 operation in the format
3
3
shown to the left. Type 5 switch groups require one
3
3
control module and one monitor module. Type 5 switch
5
5
groups can be used for fans or dampers. The control module is used for the ON control of the fan.
The monitor module is used for the ON verification of the fan. Type 3 switch groups require one
control module and two monitor modules. Type 3 switch groups are usually only used for dampers.
SCE-8
The control module is used for CLOSED control of a damper, one monitor module is used for the
OPEN verification of the damper and the other monitor module is used for the CLOSED verification
of the damper.
When used with an SCE, eight switch groups are
available for group type 8 operation and eight are
8
1
available for group type 1 operation in the format
8
1
shown to the left. Type 8 switch groups require two
8
1
control modules and one monitor module. Type 8
8
1
switch groups can be used for fans or dampers. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 1 switch groups require one control module and one monitor module.
SCE-8
Type 1 switch groups can be used for fans or dampers. The control module is used for OFF control of
a fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 8 operation and eight are
8
8
available for group type 1 operation in the format
1
1
shown to the left. Type 8 switch groups require two
1
1
control modules and one monitor module. Type 8
8
8
switch groups can be used for fans or dampers. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 1 switch groups require one control module and one monitor module.
SCE-8
Type 1 switch groups can be used for fans or dampers. The control module is used for OFF control of
a fan and the monitor module is used for the OFF verification of the fan.
When used with an SCE, eight switch groups are
available for group type 8 operation and eight are
8
2
available for group type 2 operation in the format
8
2
shown to the left. Type 8 switch groups require two
8
2
control modules and one monitor module. Type 8
8
2
switch groups can be used for fans or dampers. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 2 switch groups require one control module and one monitor module.
SCE-8
Type 2 switch groups can be used for fans or dampers. The control module is used for OFF control of
a fan and the monitor module is used for the ON verification of the fan.
When used with an SCE, eight switch groups are
available for group type 8 operation and eight are
8
8
available for group type 2 operation in the format
2
2
shown to the left. Type 8 switch groups require two
2
2
control modules and one monitor module. Type 8
8
8
switch groups can be used for fans or dampers. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 2 switch groups require one control module and one monitor module.
SCE-8
Type 2 switch groups can be used for fans or dampers. The control module is used for OFF control of
a fan and the monitor module is used for the ON verification of the fan.
When used with an SCE, eight switch groups are
available for group type 8 operation and eight are
8
3
available for group type 3 operation in the format
8
3
shown to the left. Type 8 switch groups require two
8
3
control modules and one monitor module. Type 8
8
3
switch groups can be used for fans or dampers. One control module is used for the ON control of the
fan, the other control module is used for the OFF control. The monitor module is used for the ON
verification of the fan. Type 3 switch groups require one control module and two monitor modules.
SCE-8
Type 3 switch groups are usually only used for dampers. The control module is used for CLOSED
control of a damper, one monitor module is used for the OPEN verification of the damper and the
other monitor module is used for the CLOSED verification of the damper.
Table 3.5 FSCS Mode Dipswitch Settings (4 of 6)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
*
SCS Series Manual — P/N 15712:L 7/18/16
Configuration

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scs-8Scs-8l

Table of Contents