Honeywell NOTIFIER SCS Series Operation And Installation Manual page 51

Smoke and hvac control station
Table of Contents

Advertisement

SCS-8L⁄SCE-8L Installation
LDM-R32
EIA-485
Communication between the FACP and the SCS-8L is accomplished over a two-wire EIA-485 serial interface. Up to 32 EIA-485 devices
may be installed on an EIA-485 circuit. The data communication and wiring are supervised by the fire alarm control panel. All SCS-8L
Smoke Control Stations must be in the same room as the FACP/Network Annunciator when in FSCS mode.
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion from the control panel to the SCS-8L. The maximum wir-
ing distance between the panel and the last SCS-8L or annunciator is 6000 feet @ 16 AWG. However, all SCS-8L⁄SCE-8L modules must be
contained in the same room with the FACP/Network Annunciator when in FSCS mode. The wiring size must be a 12 to 18 AWG twisted pair
cable having Characteristic Impedance of 120 ohms, +/-20% (Shielded cable is recommended). Limit the total wire resistance to 100 ohms
on the EIA-485 circuit, and 10 ohms on the SCS-8L power circuit. Do not run cable adjacent to, or in the same conduit as, 120 volts AC ser-
vice, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or
SCR power circuits.
Terminal Wiring
The following should be considered when connecting terminal wiring:
Do not "T-Tap" the EIA-485 circuit; it will not function properly. Wire it as shown in Figure 3.27.
Install the built-in 120 ohm resistor on the SCS-8L module if it is located at the physical end of the EIA-485 Loop, by turning ON
dipswitch 8 on the SCS-8L. Turn OFF dipswitch 8 on all other SCS-8L modules. If an EIA-485 device other than an SCS-8L⁄SCE-8L is
at the physical end of the EIA-485 loop, install a R-120 resistor across the EIA-485 out terminals of the device and ensure that
dipswitch 8 is turned OFF on all SCS-8L modules.
Connect Earth Ground to a mounting screw on the backbox or cabinet.
Connect 24 VDC Power to the SCS-8L. This power need not be supervised by a power supervision relay since it is inherently
supervised by the control panel (loss of communications is registered during loss of power to the SCS-8L).
When the EIA-485 shield is in conduit: Connect it to the system reference (system common). The shield can enter the cabinet, but must be
insulated from the cabinet (no electrical contact). Between Smoke Control Stations, wire-nut multiple shields together and insulate. Treat the
shield like a system wire making certain it does not come in contact with other wires or earth ground.
SCS Series Manual — P/N 15712:L 7/18/16
SCS-8L
Figure 3.24 LDM Ribbon Cable Connection
The SCS⁄SCE
SCS-8L LDM-R32
51