AEG ME09 Installation, Operation And Maintenance Manual page 53

5000a-6400a
Table of Contents

Advertisement

2.3
2.3.1
2.3.2
2.12
2
L1、L
、L3,
L1、L2、L3
L1、L2、L3
L1、L2、L3
L1、L2、L3
L1
...
L3
-
-
0.00
A
1
V
kW
kVAR
kVA
1
AUTO
)
1
AUTO
)
Hz
%
999 MWh
TRIP UNIT
2.3 OTHER modes
2.3.1 METERING MODE
METERING Mode is available on all trip unit types (Mpro S &
Mpro N ) and can be used to access and to indicate the electrical
parameters of the circuit in which the circuit breaker is
installed..
2.3.2 METERING FUNCTIONS
The Mpro S Trip Units are always supplied with an Ammeter
that measures and indicates the current in the L1, L2 & L3
phases and the neutral.
The Mpro N Trip Units is supplied with a unit that measures the
parameters and units as indicated in table 2.12. To access all
voltage related parameters the Trip Unit must be supplied with
voltage signals by using external single pole poten al
transformers. These must be selected and connected In
accordance with the characteris cs of the power supply (Wye
orDelta). For a power supply with a Wye construc on the
chosen condi oners must use V=L-N and for a Delta
construc on type V=L-L.
Poten al Transformers are available as ME09 accessories and
are mounted and connected externally.
Note: Energy reset is supported from setup
so ware and over communica ons.
Table 2.12
Pa ra meter
Pha se
Current
Phase L1, L2, L3, neutral
Voltag e
L1, L2, L3 (Note 1)
Real Power
L1, L2, L3 and total
Reactive Power
L1, L2, L3 and total
Apparent Power
L1, L2, L3 and total
Peak Power
Total
Demand
Energ y
Phase L1... L3 and total
Frequency
-
Power Factor
-
1) Auto-ranging from 0.00 to 999 MWh
2.
3
Unit
A
V
kW
kVAR
kVA
1
AUTO
)
1
AUTO
)
Hz
%
2.3-01