1.1-05
INTRO
BREAKER
TRIP UNIT
LOCKS
ACCESSORIES
Through-door Racking:
The breaker racking mechanism is accessible through the front
door and permits safely disconnec ng/withdrawing the circuit
breaker without opening the door and exposing personnel to live
parts during the process.
Padlocking devices:
5000-6400A Power Circuit Breakers are supplied with several
padlocking devices. The breaker in xed and draw-out pa ern
have a padlocking facility for one padlock of 5-8 mm allowing
the breaker to be locked in its OFF posi on.
The casse e supplied with the breakers in drawout mode has
three facili es for up to 3 padlocks of 5-8 mm.
Two of these can be found on the casse e euchenon and can be
used for locking the shu ers in closed posi on and/or closing
and locking the racking handle aperture.
The third op on is located on the breaker drawout support
slides and can be used to lock breaker & chassis combina on in
disconnected posi on
Facia Pushbu on Padlocking Facili es:
To prevent un-authorized access to both the ON and OFF push
bu ons on the breakers front facia, a padlock able push bu on
cover can be xed to the breaker front facia.
1 padlock of 5-8 mm can be used.
Key Locking mechanism
Mul ple kits are available allowing the use of Ronis, Profalux or
Castell Key locks. Both the breaker and casse e can be
equipped with these facili es. The breaker can accept
mechanisms allowing the use of up to four Ronis or Profalux
locks or one Castell lock that allow one to lock the device in OFF
posi on.
The casse e only accepts mechanisms allowing the use of Ronis
and/or Profalux locks that can be used for breaker posi on
and/or shu er locking.
Shu ers:
All casse es are supplied with lockable safety shu ers.
Casse e Posi on Indica on Contacts:
This op onal casse e/substructure device permits local or
remote indica on of the circuit breaker status(CONNECTED,
TEST, DISCONNECTED. (Set of 3 or 6 single-pole changeover
contacts are available).
Li ing Truck and Adapter:
Op onally available to facilitate breakers handling. an adapter
being available allowing one to use the same device for
envelope 3 devices.
TESTS
APPENDIX

Advertisement