Installation instructions / ACS-2 plus
Settings for netwerk connection with Ethernet card:
As described previously, the following settings must be carried out:
Event protocol
Baud rate 19200
MVA (virtual address of the current controller from NetEdit).
DVA (virtual target address of the computer communicated with that of the controller = MVA
of the corresponding computer from NetEdit).
Dependencies:
1.
If at least one of the DIP switches 6 and 7 of the S1 switch block (see 8.5.1) is set to ON, the
DIP switch settings have priority. This means that areas which cannot be modified via the
setup contain a corresponding note and the individual parameters cannot be selected.
2.
When using the interface of the ACS-2 plus controller for RDT, the interface is already used
by the RDT protocol.
Procedure:
10.2 Defining the controller in IQ NetEdit
After hardware installation (mounting and wiring the controllers) and setting the hardware parameters
(controller address, baud rate, protocol) using the DIP switches or the ACS-2 plus setup, the devices must then
be defined in the access control software.
(See also chapter 8.6 = DIP switches and the corresponding documents of the used interface cards).
Transferring the hardware configuration to the access control software is done by a special configuration
program which is part of the access control software. Detailed examples how to configer an ACS-2 plus
controller can be found in the manual of the configuration software.
Example:
1.
9-bit AC/CU prot.
2.
DIN prot.:
3.=>RDT prot.
4.
Event prot.
Status: Addr: 32; 19200 Baud
*** Defined by DIP switch! ***
Press <Enter>...
- Disconnect the RDT cable from the ACS-2 plus
- Connect the "setup" cable
- Carry out the boot login
51