Honeywell ACS-2plus Installation Instructions Manual page 41

Table of Contents

Advertisement

Installation instructions / ACS-2 plus
Adjusting the end-of-charging voltage
1.
The power supply must have reached the operating temperature.
This requires the power supply to be switched on for at least two hours with rated load and closed
housing.
2.
Connect the charged battery.
An incompletely charged battery leads to an incorrect adjustment!
3.
Adjust the voltage at the battery terminals by means of the RV2 potentiometer under consideration
of the ambient temperature according to the table below.
Make sure of the battery type!
1.
After having measured the temperature
2.
If the battery voltage deviates by >200mV from the nominal value, then adjust PO4 accordingly.
Warning! Destruction of device possible!
Ensure that only the PO4 potentiometer is adjusted...