The voltage diagrams 1 and 2 compare the effects of two cable cross-sections.
The required line cross-section must be calculated using the graphs shown above.
Note! Pay attention to legal rulings!
The local requirements must be observed for the line cross-section. VDE 0100 applies to
Germany. The output fuse of the power supply unit must have the appropriate current rating. The
highest current rating is determined by the smallest line cross-section of the supply cable.
Installation instructions / ACS-2 plus