Honeywell Midas-M User Manual page 88

Hide thumbs Also See for Midas-M:
Table of Contents

Advertisement

ModBus
Information R/W
Register
Number
40006
Channel
Enabled State
40007 to
Gas
40008
Concentration
Ch1
40009 to
Gas
40010
Concentration
Ch2
40011 to
Gas
40012
Concentration
Ch3
40013 to
Gas
40014
Concentration
Ch4
40015 to
Gas
40016
Concentration
Ch1
40017 to
Gas
40018
Concentration
Ch2
40019 to
Gas
40020
Concentration
Ch3
40021 to
Gas
40022
Concentration
Ch4
Midas-M
Data
Data
Size
Type
(Byte)
R
u16
2
R
f32
4
R
f32
4
R
f32
4
R
f32
4
R
u32
4
R
u32
4
R
u32
4
R
u32
4
Description
This is the bit
bit 0 : Ch1 Dummy cell bit 1 : Ch1
representation
Disabled bit 2 : Ch1 Reserved for
information of
futher expansion bit 3 : Ch2 Dummy
channel
cell bit 4 : Ch2 Disabled bit 5 : Ch2
enabled. If
Reserved for futher expansion bit 6 :
dummy cell is
Ch3 Dummy cell bit 7 : Ch3 Disabled
attached or
bit 8 : Ch3 Reserved for futher
channel is
expansion bit 9 : Ch4 Dummy cell bit
disabled bit
10 : Ch4 Disabled bit 11 : Ch4
value is set.
Reserved for futher expansion bit
12~15 : for future expansion
Value in float
Value in float
Value in float
Value in float
Value in fixed
Conversion equation: ppm value =
point
Value * 1/10 DECP
Value in fixed
Conversion equation: ppm value =
point
Value * 1/10 DECP
Value in fixed
Conversion equation: ppm value =
point
Value * 1/10 DECP
Value in fixed
Conversion equation: ppm value =
point
Value * 1/10 DECP