QUICK
REFERENCE
GUIDE
MIDAS M MULTI GAS TRANSMITTER
Fixed Single Point Extractive
Multi Gas Transmitter
3016M5000 Rev 01

Advertisement

loading

Summary of Contents for Honeywell MIDAS-M

  • Page 1 QUICK REFERENCE GUIDE MIDAS M MULTI GAS TRANSMITTER Fixed Single Point Extractive Multi Gas Transmitter 3016M5000 Rev 01...
  • Page 2 Introduction The Midas M® is a Fixed Extractive Single Point with 4-in 1 Multi Gas Detector that draws a sample locally or from a remote point to a sensor cartridge that is located inside the detector’s chassis. A wide range of toxic, flammable and oxygen gas sensor cartridges are available that enable detection of gases used or generated in the Semiconductor and other manufacturing industries.
  • Page 3: What's In The Box

    Sécurité MISE EN GARDE Le non-respect des précautions suivantes peut causer des blessures cor- porelles ou des dégâts matériels: • Pour minimiser les risques de charge électrostatique, veillez à ce que la mise à la terre soit adéquate et installez l’équipement de manière à éviter toute décharge accidentelle.
  • Page 4 Overview Pump Module Main Module Sensor cartridge Mounting bracket assembly...
  • Page 5 Device Status LED’s Device Status Icons Channel #1 Status Channel #2 Status Channel #3 Status Channel #4 Status Power LED Bar graph for gas concentration display Alarm 1 LED Entry indicator for menu operation Alarm 2 LED Gas concentration Fault LED Unit Selected channel number Gas name, menu, fault message...
  • Page 6 Mounting the Transmitter Device Open the door Remove two screws Carefully pull main chassis forward Drill two holes 2.2 in • Partially screw the fixings into the mounting surface. • Place the mounting bracket assembly over the screws, so they pass through the mounting holes and then slide down to locate in the slots.
  • Page 7 Mounting the Transmitter Device • Align the rounded corner at the lower of the main module with the sim- ilar rounded corner at the bottom of the mounting bracket assembly • Slide the main module backward while pushing the main module up after connecting with a mounting bracket so that the PCB and con- nector and tubes engage simultaneously.
  • Page 8 Mounting the Transmitter Device Remove the internal packing card securing the pump. Failure to remove this packing will result in damage to the Midas M detector.
  • Page 9: Electrical Installation

    Electrical Installation Access for the electrical wires to the terminal module is made via the PG16 cable gland located at the bottom of the mounting bracket assembly. The cable gland can be removed and replaced with a suitable conduit fitting if required.
  • Page 10 4-20mA Analog Output Switches (4 Channels) Relay Contact Terminals 4-20mA Analog Output Switches (4 Channels) 24Vdc Power Terminals Optimal Relays Connector RJ45 Connector Power Switch Cable Gland The terminals used are suitable for conductors of 24 to 14 AWG (0.5 to 1.8mm Dia.).
  • Page 11: Mise En Service

    Comissioning WARNING Before carrying out any work, ensure local and site procedures are followed. Ensure that the associated control panel is inhibited to prevent false alarms. The following procedure should be followed carefully and only performed by suitably trained personnel. 1.
  • Page 12: Specifications

    3. Assurez-vous que l’interrupteur marche / arrêt est situé au bas de la fixation. le support est en position de marche. 4. Mettez le système sous tension. 5. Après la routine de démarrage, le détecteur affichera le mes- sage normal mode de fonctionnement. 6.
  • Page 13 Weight 0.31 kg (0.68 lb) Power Requirements: Operating Voltage 24 VDC Nominal 15 to +10% (20.4 to 26.4 VDC) Operating Voltage with Power over Ethernet (PoE) 48 VDC PoE (IEEE 802.3af compliant) Power Consumption: Transmitter unit Typ. 5W (normal condition)¹ Transmitter unit <...
  • Page 14 Contact Us Asia Pacific Honeywell Analytics Asia Pacific Co. Ltd. 7F SangAm IT Tower, 434 Worldcup Buk-ro, Americas Mapo-gu, Seoul 03922 Honeywell Analytics South Korea 405 Barclay Boulevard Lincolnshire, IL 60069 Mainland China Tel: +1 847 955 8200 Honeywell Industrial Safety Gas Detectors...