Overriding Delays At Level 1; Sounder Fault Monitoring - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels
When shown on the display, the letter 'P' appears in front of the address. This indicates the output is
on the peripheral bus. A letter is added after the address to indicate relay A, B, C or D.
When peripheral bus units are used, their zone programming selection is shown by using the same
'Sounder' option as the on board and loop-driven outputs. For example, a sounder circuit controller
SCC module wired onto the peripheral bus with an address of 11 may be shown as:
---------------------------------------------
This shows that all sounders wired into the output 'B' of the sounder circuit controller wired onto the
peripheral bus at address 11 will use ringing pattern 004.
An auto-learn must be performed on the peripherals before they will be added to the list
of sounder circuit outputs.
Refer to the 4-Way Sounder Installation Guide for further information.

5.4.5 Overriding Delays at Level 1.

EN54-2 7.11d
EN54
Override delays at
Level 1.

5.4.6 Sounder Fault Monitoring

Once commissioned any open or short circuits occurring on any of these inputs, either on-board or
remote, are automatically detected, recorded in the event log and displayed. For example:
---------------------------------------------
SHORT CIRCUIT ON SOUNDER B
Commissioning Manual
[ Panel in Commissioning mode ]
SOUNDER
P:011:B
It shall be possible to override all delays to outputs at Level 1. Refer
to Section 16.2 for further information.
If ZX1Se, ZX2Se, ZX5Se and ZX10Se panels are to be configured
with delays to outputs a manual call point (MCP) will be located
next to the panel to enable any delays to be overridden.
[ Panel in Commissioning mode ]
Document No. 996-175-000-1, Revision 01
Pattern
004
MORLEY-IAS
Page 35