Calibrate; Zones; Devices; Changing Device Information - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

MORLEY-IAS
Pressing any key then restores the display to the normal commissioning menu.
The Auto Learn sequence can be used as many times as required and does not affect the text
description used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the 'Devices' option to
obtain detailed information on the device type and to see the address of each device
found on the loop.

5.3.2 Calibrate

The calibrate function is identical to the routines described in Signalling Loops Section. Refer to
Section 5.2.2.

5.3.3 Zones

The Zone function is identical to the routines described in Signalling Loops Section. Refer to Section 5.2.3.

5.3.4 Devices

The 'Devices' option presents detailed information for the various types of peripheral device fitted on
the bus.
Address
---------------------------------------------
P:012
Input unit
Device Type
The signal from the peripheral device is fixed at 16. It will drop to 0 if communications or
power to it is lost.
5.3.4.1

Changing Device Information

Changes are made by first pressing the 'Change' key. The display will present a menu of options that
can be changed, as follows:
---------------------------------------------
1)Sensor Text
Select the required option by pressing the appropriate number. Press the 'No' key to return to the
normal, device information display.
If only the device text can be changed, the display will jump straight to the location text.
Page 28
Zone
Location Text
[ Panel in Commissioning mode ]
Z003
"BOILER ROOM
S= 16
Analogue Signal
[ Panel in Commissioning mode ]
2)Zone
6)Action
7)Group
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
"
D8..D1= 00000001
Digital inputs status
1=Logic High 0=Logic Low
3)Event
9)Mode
Commissioning Manual