The alarm verification feature should not be used as a substitute for proper detector
location/applications or regular system maintenance. Alarm verification features are
intended to reduce the frequency of false alarms caused by transient conditions. They are
not intended to compensate for installation design errors or lack of maintenance.
Keep the verification delay to a minimum. A maximum delay of 5 secs is recommended.

11.4.1 Commissioning Verification Mode

Press '3' to select Verification mode from the 'Day Modes Menu. The display will prompt whether the
mode is to be used.
---------------------------------------------
Press 'No' to inhibit the mode and return to the 'Day Mode' menu.
Press 'Yes' to enable the mode. The display will then prompt the start and end times for the day period.
---------------------------------------------
START at
Press 'Yes' to accept and step on. Press 'No' to change and then enter the required start time using
the number buttons.
---------------------------------------------
START at
Press 'Yes' to accept and step on. Press 'No' to change and then enter the required end time using
the number buttons. The display then prompts how long to delay the alarm.
---------------------------------------------
Verification delay =
Enter the desired delay (see above guidelines for maximum times).
When the event log is set to 'Normal' the panel will record the high, analogue output
signal from the detector that initiated the verification timer. If the detector is still in alarm
at the end of the verification delay, a fire alarm will be recorded in the log. With the event
log in 'Diagnostic' the panel will record all analogue signals received from the detector
until the smoke level drops back to normal.
Page 46
[ Panel in Commissioning mode ]
Allow mode
?
[ Panel in Commissioning mode ]
6:30
?
[ Panel in Commissioning mode ]
6:30
[ Panel in Commissioning mode ]
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
FINISH at 17:45
0 s ?
?
Commissioning Manual

Advertisement

Table of Contents
loading

Table of Contents