ZX Fire Alarm Control Panels
5 Configure Option
5.1 Accessing the Configure Option
•
Page 1 of the Commission menu is shown below:
----------------------------------------------
1)CONFIGURE
2)Inspect
•
The CONFIGURE option allows the Signalling Loops, peripherals, sounders and relays to be
programmed. It also enables the function to allow the panel to be programmed by a PC.
•
Press '1' to select the 'CONFIGURE' option.
The CONFIGURE option and all sub menu options require the Memory Lock to
be open.
•
The display then shows a menu of options as follows:
----------------------------------------------
CONFIGURE : Loop 1) 2) 3) 4) 5)
6)Peripherals
NOTE: The menu will only show the number of signalling loops programmed during setup (Refer to the Setup
Option). The ZX2Se can only have two loops maximum.
5.2 Signalling Loops
•
After selecting a loop from the configure menu, the display will present a list of options as follows:
----------------------------------------------
CONFIGURE : Loop 1)
2)Devices
The words 'CONFIGURE: Loop 1' on the top line of the menus provides a reminder that
panel is in configuration mode, with loop 1 selected.
•
Select the required option by pressing the appropriate numeric key.
•
When commissioning a new panel, start by performing an 'Auto Learn'. This will cause the panel to
search for all devices installed on the loop.
Commissioning Manual
[ Panel in Commissioning mode ]
YES)More Options
3)NORMAL OPERATION
[ Panel in Commissioning mode ]
7) Sounders 8)Relays
[ Panel in Commissioning mode ]
1)Zones
3)Auto Learn
Document No. 996-175-000-1, Revision 01
9)PC
4)Calibrate
MORLEY-IAS
[1]
[1]
[1]
Page 15