Portb Protocols; Table 13 - Master Panel Network Settings - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

MORLEY-IAS
Network Option
Panel network-address
number
Quantity of slave
processors
Slave CPU 1 is at
network address
Slave CPU 2 is at
network address
Etc.
Use modem
Share zones
Peer-to-Peer
Port B Protocol *
System events
For full information on how to commission and program a network installation, refer to
document P/N 996-075.
13.2 Port B Protocols
NOTE: * Port B Protocol is not available on ZX1Se or ZX2Se panels.
The Port B serial interface supports a number of different protocols.
These can be used to define the connections as:
1.
Standard MORLEY-IAS Panel Network / Graphics PC Interface
2.
Pager Interface
3.
Other PC System Interface
The following table defines the settings to be entered for each interface type.
Page 50
Option setting
1 to 99
1 to 99
1 to 99
1 to 99
[TRUE]/[FALSE]
[TRUE]/[FALSE]
[TRUE]/[FALSE]
0
[GLOBAL]/[LOCAL]
Table 13 – Master Panel Network Settings
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
Comments
Enter Master's own address, e.g.. 4.
Number of slaves DIRECTLY connected to the Master, i.e.
via port C.
The address of the first slave panel.
The address of the second slave panel.
Set to TRUE if a modem is connected to port C.
Zones are shared between panels
Allow MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses from a slave panel.
Use default of 0 unless special applications interface.
Global -
1.
Passes system events over network
2.
Accepts other network events
Local -
1.
Does not pass events over the network.
2.
Ignores other network events
NOTE: The zoned fire status is passed over a shared-zone
network regardless of events being global or local.
Commissioning Manual