7.3 Crystal

The bus operating frequency is precisely measured during manufacture. The measured value is
marked on the CPU board.
This option allows the measured crystal frequency to be entered into the memory so that the software
can employ an adjustment factor to maintain an accurate date and time clock.
To select the option, press '7' and the display shows:
---------------------------------------------
Timer crystal frequency = 3.68678 MHz ok ?
If the frequency is correct, press 'Yes' to return to the previous menu.
If the frequency is not as marked on the CPU, press 'No' and enter the least-significant three digits
using the number keys.
Increasing the number by one will make the time clock lose two seconds per week. Decreasing the
number by one will give a gain of two seconds per week.
Page 38
[ Panel in Commissioning mode ]
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
Commissioning Manual