ZX Fire Alarm Control Panels
•
This display shows several pieces of information. To avoid ambiguity as to what can be modified, the
display will flash the item that can be changed. If this item is a number and you want to change it, then
simply type the new value over the top. If the item is not numeric, then use the 'Change' key to make
your change. For example.
Pattern ON
•
On entry, the 'to zone' number (i.e. 80 in this example) will be flashing to show this item can be
changed, if required. To make this zone 12, enter '12' using the number keys. The display will then
show the new zone range.
---------------------------------------------
Pattern
•
RESULT: Sounder circuit controller A will be immediately activated if a fire is detected in zones 1, 2, 3,
4, 5, 6, 7, 8, 9, 10, 11 or 12.
5.4.2.2
Pattern OFF
•
The display will then automatically flash the next changeable item, which is the mode of operation. As
this is not numeric, use the 'Change' key to change the mode. Each press of the change key will cycle
through each of the possible operating modes for this output. For example.
---------------------------------------------
Pattern
•
RESULT: Sounder circuit controller A will not be activated if a fire is detected in zones 1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11 or 12.
5.4.2.3
Pattern DELAY
•
The '>' key can be used to move across the display. For example, if the mode is flashing 'Delay' then
the delay period can be modified by pressing the '>' key to select the delay time value. Then enter the
desired period using the number keys. The backspace '<' key moves back one digit - useful for
correcting errors when entering numbers.
---------------------------------------------
Pattern
•
RESULT: Sounder circuit controller A will be activated 10 seconds after a fire is detected in zones 1,
2, 3, 4, 5, 6, 7, 8, 9, 10, 11 or 12.
•
Delays can be set in multiples of 10 seconds up to 1800 seconds (600 seconds is the maximum time
allowed in the EN54 standard).
Zone 1 Call Point
in Alarm
Zone 1 Sensor 1
in Alarm
Pattern
Validated
SOUNDERS
OFF
Commissioning Manual
[ Panel in Commissioning mode ]
zone
3
001 to 012
[ Panel in Commissioning mode ]
zone
3
001 to 012
[ Panel in Commissioning mode ]
zone
3
001 to 012
10 S
SOUNDERS
ON
Document No. 996-175-000-1, Revision 01
MODE
ON
MODE
OFF
MODE
DELAY FOR
0010s
MORLEY-IAS
Page 31