MORLEY-IAS
3.5 Enabling Level 2 or Level 3 Access
•
To enable Level 2 or Level 3 operation, press the SHIFT key. The display will then show:
[Panel ACTIVE Control Keys INHIBITED]
Do you want to enable the control keys?
•
Press the 'Yes' key and the display will prompt for entry of the password.
[Panel ACTIVE Control Keys INHIBITED]
Please Enter Password
•
Enter the 4-digit, Level 2 password. The display then shows the Main Menu of user options.
----------------------------------------------
[ACTIVE]
4)Enable
•
If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display
showing the system status message. To re-show the menu display, press the 'SHIFT' key.
•
If a key has not been pressed for a specified period of time, (normally 5-minutes – programmable),
then 'Level 2' access will be automatically cancelled. It will be necessary to re-enter the password to
re-activate Level 2 functions.
Note: As a commissioning aid the level 2 automatic timeout can be disabled at access level 3
(refer to Section10 Passwords Option). Leaving the panel in this state is not recommended
and must only be done with the written agreement of the local fire officer.
•
For detailed information on the Level 2 user options, refer to the User Manual (P/N 996-182-000-X).
3.5.1 Selecting the commissioning option
•
To access the commissioning functions in the panel, press '1' to select the commission option.
•
The display will prompt for entry of the Level 3 password. Enter the Level 3 password using the
numeric keys.
•
The display will then show the commissioning menu options.
Page 10
03-Mar-2007
All devices are inside working limits
03-Mar-2007
All devices are inside working limits
[ Keypad available for user access ]
1)Commission 2)Test
5)Disable
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
11.38
11.38
3)Time
6)Print
7)View
[1]
[1]
[1]
Commissioning Manual