Access Levels 2; Operating Instructions For Access Level 2 Functions - Honeywell 13270-01LB Data, Installation And Commissioning Manual

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Fire Panels

Access levels 2

To configure the system enter the
appropriate access code.
NOTE: It is only necessary to
enter the access code once,
provided the 2 minute timeout is
not exceeded between button
presses.
Operating Instructions for AL2 functions
How to do a Display test
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and display buttons and check that all indicators are lit.
How to set the panel to operate in Test mode A
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and 3 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested without an alarm of fire
How to set the panel to operate in Test mode B
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and 4 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested with 2 seconds alarm of fire.
How to cancel Test mode A/B
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and 5 buttons followed by the number of the zone to have test mode cleared.
- The test mode A or B is cancelled.
How to disable a zone
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and 1 buttons followed by the number of the zone to be disabled.
- Check that the appropriate Zone fault indicator and the Disabled indicator are lit.
- A detected fire in the disabled zone will not cause the panel to go into fire condition.
How to enable a zone
q Enter the AL2 access code and check that the Access/function lamp is lit.
q Press the shift and 2 buttons followed by the number of the zone to be re-enabled.
- The previously disabled zone is re-enabled.
4188-424 issue 4_Part 1_10-09
Access codes
Factory set codes are:
Access level 2 Code : 123
Depending on how the system is
configured coded entry may be
necessary for test.
The factory codes can be
changed at any time after power
up.
12
Access levels 2
NOTE: It is important to leave
the system in a normal
operating condition on
completion of commissioning.
NOTE: The auxiliary contacts do
not operate in the Test Modes.