Figure 2-2 Redundant Fsc-Sm Ucn Cabling - Honeywell FSC-SM Installation Manual

Safety manager
Table of Contents

Advertisement

2.5
Cabling Installation,
FSC-SMM cabling,
continued
NIM
A
B
CAUTION
Cable continuity, or communication will be lost to other UCN devices.
Make sure the torque specification will be 12 - 15 inch pounds to comply to UCN
connector specifications.
30
Figure 2-2 illustrates the UCN cabling required of a redundant FSC Safety
Manager system.
In this case two FSC-SMM modules are installed, one in each Central
Part. RG-6 UCN drop cables are run from the drop ports on UCN A to
UCN A F-style connectors of each FSC-SMM. RG-6 UCN drop cables are
also run from the drop ports on UCN B to UCN B F-style connectors of
each FSC-SMM.
For detailed information on cabling requirements, refer to the
Integration Guidelines for FSC System Cabinets.
Figure 2-2 – Redundant FSC-SM UCN cabling
UCN A RG-11
A
A
RG-6
Drop Cables
B
B
UCN B RG-11
Remove the UCN cable from the FSC-SMM port without breaking UCN
FSC Safety Manager Installation Guide
Continued
A
B
A
B
Honeywell
CP 1
CP 2
Continued on next page
A
B
10/01