2.4
Cabling Considerations,
Spacing, continued
Table 2-4 – Tray spacing
Cable
Class
Data 1
Data 2
Data 3
Data 3A
Data 4
Data 4A
Table 2-5 – Tray/conduit spacing
Cable
Class
Data 1
Data 2
Data 3
Data 3A
Data 4
Data 4A
26
Data 1
Data 2
mm (in.)
mm (in.)
Note 2
Note 2
152.4 (6)
152.4 (6)
152.4 (6)
152.4 (6)
660.4 (26)
457.2 (18)
660.4 (26)
660.4 (26)
Note the following considerations:
ATTENTION
• Note 1:
– Data 3 and Data 4 cables may be run in a common tray but should be
separated by a barrier. This barrier does not have to be grounded.
• Note 2:
– Data 1 and Data 2 cables may be in a common tray, provided they are
separated by a grounded steel barrier.
Data 1
Data 2
mm (in.)
mm (in.)
25.4 (1)
25.4 (1)
101.6 (4)
101.6 (4)
101.6 (4)
101.6 (4)
457.2 (18)
304.8 (12)
457.2 (18)
457.2 (18)
FSC Safety Manager Installation Guide
Continued
Data 3
Data 3A
mm (in.)
mm (in.)
152.4 (6)
152.4 (6)
152.4 (6)
152.4 (6)
0.0 (0)
0.0 (0)
Note 1
203.2 (8)
304.8 (12)
457.2 (18)
Data 3
Data 3A
mm (in.)
mm (in.)
101.6 (4)
101.6 (4)
101.6 (4)
101.6 (4)
0.0 (0)
0.0 (0)
0.0 (0)
152.4 (6)
203.2 (8)
304.8 (12)
Data 4
Data 4A
mm (in.)
mm (in.)
660.4 (26)
660.4 (26)
457.2 (18)
660.4 (26)
Note 1
304.8 (12)
203.2 (8)
457.2 (18)
0.0 (0)
0.0 (0)
Data 4
Data 4A
mm (in.)
mm (in.)
457.2 (18)
457.2 (18)
304.8 (12)
457.2 (18)
0.0 (0)
203.2 (8)
152.4 (6)
304.8 (12)
0.0 (0)
0.0 (0)
Continued on next page