1.3
Move Preparation,
Cabinet entry
10/01
Continued
The process signal cables can enter the FSC Safety Manager cabinet
through the top or bottom of the cabinet. The FSC-SM cabinet is prepared
for field termination assembly to interface boards (FTA-E) or terminals
(FTA-T). These interface boards or terminals may be located in the
FSC-SM cabinet or in cross-wiring cabinets next to the FSC-SM cabinet.
Figures 1-3 through 1-8 illustrate the placement and dimensions for
process wiring for FTAs located in the FSC-SM cabinet.
The FSC-SM cabinet is also prepared for top or bottom entry as per user
specification. For bottom entry, sliding floor plates are provided which can
be adjusted to provide entry slots. For top entry, one sliding plate is
provided which can be adjusted to provide entry slots. For top or bottom
entry, the cables should be clamped firmly to the cabinet. The clamping
devices should be able to withstand a 45 kg (100 lb) pull. This prevents
damage inside the cabinet when pulling on cables outside the cabinet.
The FSC-SM cabinet includes a cable clamp rail at the bottom or at the
top.
Figure 1-3 illustrates an FSC-SM cabinet bottom configured for back
access of the I/O field cables with FTA-T.
Figure 1-3 – FSC-SM cabinet with back access (FTA-T)
Field cable duct
Turning point
swing frame
FSC Safety Manager Installation Guide
FTA-T
REAR
FSC I/O mounting rack
FRONT
TOP VIEW
Continued on next page