Node Detail Menu, Screen 3; Configuration Menu; Figure 19. Node Detail, Screen 3; Figure 20. Configuration Menu - Honeywell Limitless WMPR Series Installation And Technical Manual

Multi-protocol receiver
Table of Contents

Advertisement

Installation and Technical Manual for the
Limitless™ Multi-Protocol Receiver, WMPR Series

6.5.3 | Node Detail Menu, Screen 3

Figure 19. Node Detail, Screen 3

A description of the Node Detail "screen 3" information (see
Figure 19) is as follows:
Table 17. Node Display and Indication (Screen 3)
Display
Indication
"OK" or if an Error Code- Refer to WPS
Series Installation and Technical Manual
Diagnostic
(32305925) for Sensor Error Code defini-
tions
Limitless™ switch or sensor series (i.e.,
Node Type
Switch, WBX, WPS)

6.6 | Configuration Menu

Figure 20. Configuration Menu

The CONFIGURATION MENU (see Figure 20) can be accessed
by touching the "Configration Menu " function button as
displayed in the Action Menu (see Figure 15). Once you are in
the CONFIGURATION MENU you can choose between several
different modes. A description of the modes are as follows:
PAIR: Pairing mode is required to initiate and establish an RF
communication
link between each WMPR and a Limitless™
input. Functionality described in Section 6.8.
16 sensing.honeywell.com
PURGE: Purge mode is used to remove a Limitless™ switch
or sensor from the WMPR that is no longer needed in service.
Functionality described in Section 6.9.
MORE: Moves to next screen where there are more modes to
choose (see Figure 21).

Figure 21. Configuration Menu, continued

A description of the Configuration Menu (cont.) modes are as
follows:
NODE UPDATE RATE: The Node Update Rate is the commu-
nication rate of an analog sensor (i.e. pressure sensor) with the
WMPR receiver. The Node Update Rate for a Limitless™ switch
is more unique as it is the frequency at which the Limitless™
switch will automatically communicate with the WMPR receiver
when the switch is not being actuated/de-actuated.
If the operator is cycling the switch faster than what the update
rate is set, the auto communication will not occur. The update
rate "clock" will also be reset upon an actuation/de-actuation
of the switch so communication will happen at the next switch
activation or update rate time; whichever occurs first.
An advantage of increasing the update rate frequency is allow-
ing a faster indication of a lost RF signal between the switch/
sensor and WMPR which is important in some applications; see
Section 2.5.2 for Update Rate vs. RF Lost Indication. A disad-
vantage of increasing the update rate is that it can decrease the
battery life in the Limitless™ switch or sensor as increasing the
frequency of communication consumes more battery pow-
er. Note: Some Limitless™ Series of switches do not have the
capability to allow changing of the Node Update Rate. The rate
is adjustable based on the capability of the specific switch or
sensor being used.
NODE LCD DISPLAY: The Node LCD Display mode allows you
to change the ON/OFF time of the Node LCD display. Note:
Applicable to only Limitless™ product that has this capability.
Functionality described in Section 6.11.
FACTORY RESET RCVR: The Factory Reset Receiver mode is
used to remove/un-pair all Limitless™ inputs that were previ-
ously paired to the WMPR and thus it is being returned to the
as-manufactured condition. Functionality described in Section
6.12.
ISSUE B
32309669