Floor Standing Enclosures - Honeywell Touchpoint Pro Technical Handbook

Hide thumbs Also See for Touchpoint Pro:
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS

21.3 Floor Standing Enclosures

Ventilated enclosures must only be installed in a place that provides a Pollution Degree 2 environment, e.g. places that
afford protection from rain, snow and direct UV rays (sunlight). Such an environment would include laboratories, offices and
Control rooms.
Non-ventilated (sealed) enclosures can be installed indoors or outdoors in a Pollution Degree 3 environment, but one that
affords total protection from rain, snow and direct UV rays (sunlight).
21.3.1 Floor Standing Enclosures with and without Ventilation
Part Number
Material
Dimensions (H x W x D)
Weight
Electrical Rating
Class
Altitude
Pollution Degree
Ambient Temperature
Humidity
Ingress Protection
Part. No. 2400M2501_6
Protect from direct exposure to precipitation and sunlight.
AVERTISSEMENT
Protéger des expositions directes au soleil et de la pluie.
TPPR-V-1250
TPPR-V-1260
No Ventilation
2000 x 800 x 600 mm
201 Kg
100 – 240 VAC; 50/60 Hz; 2028 W max or 24 VDC nominal (18 – 32 VDC); 2450 W
max. W max is dependent on module and PSU configuration.
Equipment Class 1 (grounded)
2000 m ASL max. in permanently-connected continuous operation.
2 (ventilated); 3 (non-ventilated)
-25 °C to +55 °C (Remote version with PSU's)
10 to 90% RH non-condensing (ventilated), 0 to 100% RH condensing (non-ventilated)
Type 1 / IP2X (ventilated); Type 4, 12 / IP56 (non-ventilated).
168
WARNING
TPPR-V-1252
TPPR-V-1262
Natural Ventilation
2000 x 800 x 600 mm
201 Kg
TPPR-V-1254
TPPR-V-1264
Forced Ventilation
2000 x 800 x 600 mm
201 Kg
Touchpoint Pro
Technical Handbook

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tppr

Table of Contents