Value
1
If Block Active is set to 1, the Controller processes the request. If Block Active is set to 0 the Controller will not process the
request or has already processed the request.
The options for Channel Type are 105 – Input Channel and 111 – Output Channel.
11.3.3 Command Poll Registers
Command
Block Active
Poll Block
1
2
3
4
5
6
7
8
9
10
Allowed values for the Result register 41n05 (n = 0 to 9):

11.4 Command Types

Note: Function 06 cannot be used for SIL channels.
Part. No. 2400M2501_6
CONFIGURATION
105
2

Table 31. Query Poll Example

Channel Type
41001
41002
41101
41102
41201
41202
41301
41302
41401
41402
41501
41502
41601
41602
41701
41702
41801
41802
41901
41902

Table 32. Command Poll Registers

Value
0
Success
1
Command not permitted
2
Inter process communication failure
67
Failure

Table 33. Command Poll Register Values

Command Type
Description
23
Alarm Acknowledge
24
Alarm Reset
25
Set Inhibit
26
Clear inhibit

Table 34. Command Types

(Updated upon
39
request execution)
Command
Channel ID
Type
41003
41004
41103
41104
41203
41204
41303
41304
41403
41404
41503
41504
41603
41604
41703
41704
41803
41804
41903
41904
Meaning
100
(Updated upon request
execution)
Command
Result
Data
41005
41006
41105
41106
41205
41206
41305
41306
41405
41406
41505
41506
41605
41606
41705
41706
41805
41806
41905
41906
Touchpoint Pro
Technical Handbook