POTENTIAL OPERATING ISSUES
Error
Message
Code
116
Operation failed; transaction
could not be closed
117
Operation failed; response
parsing failure
118
The System ID has not been
programmed. Contact your
system administrator or service
centre.
242
The channel has reported a fault Clear the fault and try
Operation Failed – fault recovery
245
delay is active
Operation Failed – power-up
246
delay is active
Operation Failed – module is in
247
configuration state
249
Not used
250
Operation failed; kill session
denied as CCB is busy
performing critical operation
252
Operation failed; Redundant
CCB failed; power cycle the
controller and try again
253
STEL timer is reset by this
operation
254
Not used
255
Operation failed
400
Unknown error code received
from CCB. Please retry the
operation. If the problem
persists, please contact your
local service representative
Part. No. 2400M2501_6
Possible Cause
Remedial Action
Refer to Error 2
Refer to Error 2
———//———
————————//————————
The System ID is not
1. Locate and re-enter the correct System ID.
stored in the system.
2. Allocate and enter an ID if none allocated.
Default is controller serial number.
(Administrator access is required for both.)
3. Contact your service representative.
The gas detection system will continue to work
correctly, but backups cannot be restored until
the correct System ID is programmed.
Clear the fault and try again
again
Sensor is still
Retry after sensor fault recovery delay has
warming up
timed out.
Sensor is still
Retry after sensor power up delay has timed
warming up
out.
Timeout while editing
Navigate to System Setup screen and set
configuration
module to Normal state from menu.
A user has attempted
Try again after the memory update is
to end a session
completed.
while the CCB is
Check with the user at the local controller that it
updating memory as
is acceptable to log in from remote PC.
result of a
configuration request
Redundant CCB
1. Replace the CCB-R.
failed during firmware
2. Remove failed CCB until replacement can be
update
fitted. (Update CCB configuration in controller.)
3. Contact your local service representative.
Channel inhibit resets
This is a warning message to notify the user
the STEL time-
that the STEL calculation is resetting
weighted average
calculations
Retry the operation. If the problem persists,
contact your local service representative.
Please retry the operation. If the problem
persists, please contact your local service
representative.
Table 45. Error Codes and Remedies
157
Sys
Sys
Fail
Fault
Relay
Relay
X
X
X
Touchpoint Pro
Technical Handbook