How to use the integral printer

Assuming the panel has an integral printer:

To Switch On / Off the Printer

a. Press the MENU ON/OFF key.
b. Press the F1 key to select [Control].
c. Press the F3 key to select [Printer]. Check that 'Printer'
appears on the screen.
d. Press the F3 key to select [On] / [Off] and then press the
F2 key to select [Enter]. 'Printer is on/off' is displayed.

To action a Paper Feed

a. Press the MENU ON/OFF key.
b. Press the F1 key to select [Control].
c. Press the F3 key to select [Printer]. Check that 'Printer'
appears on the screen.
d. Press the F2 key to select [Paper Fd]. Note the display and
menu prompts are cleared. Printer performs 8 line feeds.

To conduct a Printer Test

a. Press the MENU ON/OFF key.
b. Press the F1 key to select [Control].
c. Press the F3 key to select [Printer]. Check that 'Printer'
appears on the screen.
d. Press the F1 key to select [Test]. Note the display and
menu prompts are cleared.
e. Check that the printer provides a listing of all the characters
it is capable of printing.

How to enable/disable Sensing

These operations are not applicable for a Network Node.
NA
It is only possible to disable a Manual Call
Point (MCP) individually, not as part of a range.
DISABLING A MCP IS NOT RECOMMENDED.
A sensing device such as a sensor or MCP in the system
can be disabled/enabled. You will need the device and loop
numbers, this information can be found in the site specifi c
documents held by the person responsible for the fi re system.
a. Press the MENU ON/OFF key.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode]. At the fl ashing
cursor using and the keypad input your PIN code and then
press the Enter button.
d. To disable a device: Press the F2 button to select
[Disable]. To enable a device: Press the F1 button to select
[Enable]. The display shows either 'Enable' or 'Disable'.
e. Press the F1 button to select [Sensing]. Notice 'Device'
followed by a fl ashing cursor appears on the display. Use
the keypad to input a device number or range (1-200).
f. Press the F2 button to select [Loop]. Notice 'Loop' followed
by a fl ashing cursor on the display. Use the keypad to input
a loop number or range (1-2).
g. Press the F2 button to select [Enter]. This is confi rmed
by: 'Device(s) enabled' or 'Device(s) disabled'. The
Disablement light is lit upon disablement of the device.