Parameter 46: Computer Fail Test - Honeywell FBII CP-220A Hookup And Installation Instructions

Central station receiver
Table of Contents

Advertisement

PARAMETER 46:
Computer Fail
Test
IF ENABLED,
PARAMETER
38 PRINTER FAIL /
MANUAL
39 COMPUTER FAIL
46 COMPUTER FAIL
TEST
Page 2-96 Section 2: Programming the CP-220A CP-220A Central Station Receiver
COMP FAIL TEST OFF
Background:
PARAMETER 46 relates to the use of PARAMETER 38, Printer Fail, and
PARAMETER 39, Computer Fail. If enabled, both of these parameters will
cause the CP-220A to enter its MANUAL mode if either the printer
(PARAMETER 38) or the Automation System (PARAMETER 39) is not
ready to accept data.
NOTE: Refer to pages 2-67 and 2-94 for information on these parameters.
PARAMETER 46 operates in conjunction with these two parameters, both
of which must be programmed [ON] if PARAMETER 46 is to be enabled.
Under this scenario, if a printer or a computer failure occurs, the CP-220A
will be unable return to its AUTOMATIC mode until the operation of the
Automation System's computer is restored.
NOTE: The CP-220A's AUTOMATIC and MANUAL modes are discussed
in greater detail on page 2-103; and in PARAMETER 40, on page
2-39.
The following table illustrates the interaction between these parameters:
UPON THE DEVICE'S
FAILURE
will cause the CP-220A to enter its
MANUAL mode if it has been
operating in its AUTOMATIC mode
With both PARAMETERS 38 and 39
enabled, the CP-220A will enter its
MANUAL mode if it has been
operating in its AUTOMATIC mode
Programming Procedures:
After entering PARAMETER 46, [COMP FAIL TEST OFF] will be
displayed with the [OFF] after [TEST] flashing. Press the NEXT key or the
MANUAL/PREVIOUS key to toggle between [COMP FAIL TEST OFF] and
[COMP FAIL TEST ON], as required.
MM/DD/YY HH:MM:SS
UPON THE DEVICE'S
The CP-220A will return to the
MANUAL/PREVIOUS key is pressed
Even if the printer restores, the CP-
220A will be unable to return to its
AUTOMATIC mode until the computer
has restored; once this is done, pressing
the
MANUAL/PREVIOUS
complete the process
Hook-Up and Installation Manual
RESTORIAL
AUTOMATIC mode if
key will

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents