Parameter 21: Rts - Honeywell FBII CP-220A Hookup And Installation Instructions

Central station receiver
Table of Contents

Advertisement

REMEMBER!
To leave the Programming
Mode at any time, press the
Esc key. Doing so will
return the CP-220A to its
normal operating mode.
Programming changes will
be stored automatically.
PARAMETER 21:
RTS
Programming Procedures:
When PARAMETER 20 is entered, [DTR HANDSHAKE OFF] will be
displayed with [OFF] flashing. Toggling between [ON] and [OFF] is
accomplished by pressing the NEXT key or the MANUAL/PREVIOUS key.
Advancing to Next Parameter:
After programming PARAMETER 20, press the N key to advance to
PARAMETER 21 – the next parameter in Category C.
The CP-220A displays the parameter just programmed ([PARAMETER
NUMBER 20]) with its first digit flashing, indicating its request for the
next parameter number. Press either:
• 2 then 1 , or
• then
• the
NOTE: When the
immediately – not its number.
RTS HANDSHAKE OFF MM/DD/YY HH:MM:SS
Background:
Like PARAMETER 20, PARAMETER 21, if enabled, provides the CP-220A
with a basic means of verifying that the Automation System's computer is
capable of communicating with it – by monitoring another voltage level
known as RTS (Request to Send). Although somewhat more complex than
the DTR technique found in PARAMETER 20, it still relies on the presence
of a voltage level from the computer to indicate that communication
between the two devices is possible. Before enabling PARAMETER 21, be
sure that the Automation System's computer is capable of providing a
sustained RTS level for use by the CP-220A for this purpose.
The default, [RTS HANDSHAKE OFF], must be used under any of the
following conditions:
• when there is no Automation System present
• if such supervision is not desired
• if the Automation System does not provide a DTR voltage level
for use by the CP-220A
NOTE: Here, RTS refers to Request to Send – the term used by the RS-232
protocol – to indicate the readiness of the CP-220A to receive data
from the Automation System's computer. See page 2-74 for
additional information pertaining to RS-232, and PARAMETER 20
for additional details on this parameter.
CP-220A Central Station Receiver
Hook-Up and Installation Manual
key and 1 , or
key
is used, the name of the next parameter appears
Section 2: Programming the CP-220A Page 2-89

Hide quick links:

Advertisement

Table of Contents
loading