Goose Remote Inputs - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

CHAPTER 4: 3 SERIES IEC61850 GOOSE

GOOSE remote inputs

SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
The firmware allows the user to map each of the digital data points received in a data set,
configured for reception, to one of 32 GOOSE remote inputs.
More than 1 GOOSE remote input can be mapped to the same data element, in a data set
belonging to a received GOOSE message.
GOOSE remote inputs can only be mapped to digital data elements.
The firmware considers a GOOSE remote input to be in the "on/off" state when the digital
data element to which it is mapped, is in the "on/off" state.
The firmware allows the user to assign a string name to each of the 32 remote inputs, and
allows the string name assigned to each remote input to be up to 14 characters.
Figure 4-6: EnerVista 3 Series Setup GOOSE Remote Inputs - 1 of 2
GOOSE CONFIGURATION VIA THE 3 SERIES MENUS