Functionality - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

IEC61850 SERVER

Functionality

4-48
CLIENT CONNECTIONS
The 3 Series relay supports up to three IEC61850 concurrent client connections.
LOGICAL DEVICES AND REPORTS
Supported buffered and un-buffered report, and the report triggers are shown in the
Supported Triggers list.
Supported Triggers
Data-change
Integrity
General-interrogation
Supported buffered and un-buffered report option fields are shown in the Field list.
Field
Sequence number
Report time stamp
Reason for inclusion
Data set name
Data-ref
Buffer-overflow (Buffered reports only)
Entry id (Buffered reports only)
Conf- revision
Report control block configuration settings are modified from the IEC61850 advanced
configurator writing directly to a CID file.
The datasets for reports are fully configurable with CDCs from any Logical Node.
CHAPTER 4: 3 SERIES IEC61850 GOOSE
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

339345

Table of Contents