PIXIT for Reporting model

PIXIT for Logging model
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
ID
Ed
Description
Rp1
1
The supported trigger conditions are
(compare PICS)
Rp2
1
The supported optional fields are
Rp3
1,2
Can the server send segmented reports
Rp4
1,2
Mechanism on second internal data change
notification of the same analogue data value within
buffer period (Compare IEC 61850-7-2 $14.2.2.9)
Rp5
1
Multi client URCB approach
(compare IEC 61850-7-2:2003 $14.2.1)
Rp6
-
What is the format of EntryID
Rp7
1,2
What is the buffer size for each BRCB or how many
reports can be buffered
Rp8
-
Pre-configured RCB attributes that are dynamic,
compare SCL report settings
Rp9
1
May the reported data set contain:
- structured data objects
- data attributes
Rp10
1,2
What is the scan cycle for binary events
Is this fixed, configurable
Rp11
1
Does the device support to pre-assign a RCB to a
specific client in the SCL
Rp12
2
After restart of the server is the value of ConfRev
restored from the original configuration or retained
prior to restart
ID
Ed
Description
Lg1
1,2
What is the default value of LogEna
(Compare IEC 61850-8-1 $17.3.3.2.1, the default value
should be FALSE)
Lg2
-
What is the format of EntryID
Lg3
1,2
Are there are multiple Log Control Blocks that specify the
Journaling of the same MMS NamedVariable and TrgOps
and the Event Condition
(Compare IEC 61850-8-1 $17.3.3.3.2)
Lg4
1
Pre-configured LCB attributes that cannot be changed
online
Value / Clarification
integrity
Y
data change
Y
quality change
N
data update
N
general interrogation
Y
Y
sequence-number
Y
report-time-stamp
Y
reason-for-inclusion
Y
data-set-name
Y
data-reference
Y
buffer-overflow
Y
entryID
Y
conf-rev
Y
segmentation
Y
Y
Send report immediately
Each URCB is visible to all
clients
Deprecated
Buffer size = 50000 Bytes
Deprecated
Y
Y
Event Driven
Fixed
N
Restored from original
configuration
Value / Clarification
NOT SUPPORTED
Deprecated
NOT SUPPORTED
NOT SUPPORTED
A–61