Dnp Device Profile; Format Codes - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

CHAPTER 3: ETHERNET INTERFACE

DNP device profile

SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PATH:
SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS > DNP PROTOCOL > DNP GENERAL
To view the list of DNP Binary Inputs please refer to the Format Codes section - FC134B - of
this Guide.
DNP 3.0 Device Profile
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name: General Electric Multilin
Device Name: 3 Series relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
□ Master
⊠ Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Data Link Re-tries:
⊠None
□Fixed at 3
□Configurable
Requires Data Link Layer Confirmation:
⊠ Never
□ Always
DNP ETHERNET PROTOCOL SETTINGS
Maximum Application Fragment Size (octets):
Transmitted: configurable up to 2048
Received: 2048
Maximum Application Layer Re-tries:
⊠ None
□ Configurable