Pixit For Goose Publish Model - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

PIXIT

PIXIT for GOOSE publish model

ID
Ed
Description
Gp1
1,2
Can the test (Ed1) / simulation (Ed2) flag in the
published GOOSE be set
Gp2
1
What is the behaviour when the GOOSE publish
configuration is incorrect
Gp3
1,2
Published FCD supported common data classes
are
Gp4
1,2
What is the slow retransmission time
Is it fixed or configurable
Gp5
1,2
What is the fastest retransmission time
Is it fixed or configurable
Gp6
-
Can the GOOSE publish be turned on / off by using
SetGoCBValues(GoEna)
Gp7
1,2
What is the initial GOOSE sqNum after restart
Gp8
1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
Gp9
1
How is the retransmission curve after a change.
A–62
Value / Clarification
N
DUT keeps GoEna=F
Relay will not send GOOSE message.
SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE, DEL, SEQ, INC, ENC, SPC,
DPC, INC, ENC. (Only the elements with FC=ST or MX will be
published).
Configured by Enervista on GoCB MaxTime (0-60000 ms)
Fixed. MinTime = 4 ms
Y
sqNum = 1
Y
Y
- sqNum = 0 New change
- sqNum = 1 -> 4ms later with TAL = 1000
- sqNum = 2 -> 8ms later with TAL = 1000
- sqNum = 3 -> 16ms later with TAL = 4000
- sqNum = 4 -> 1000ms later with TAL = Update time* x 4
- sqNum = 5 -> Update time* later with TAL = Update time* x 4
- sqNum = 6-> Update time* later with TAL = Update time* x 4
- sqNum = 7 ........
- .............
*Update time is configured in the Enervista 3 Series Setup
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE