IEC61850 CONFIGURATOR
GOOSE reception and
GOOSE transmission
4-56
Add/Remove Report Control Block
1.
Click the "Add Report" button.
The button is available in the lower side of the screen and is used to add a report
control block. (a Report can also be added by right clicking the LD entry under the IED
name in the "tree" )
The "New Report Control Block" window appears.
2.
In the "New Report Control Block" window under "Select Report Type", select the radio
button for a buffered or unbuffered report.
3.
In the "IEC61850 Clients N#" dropdown list, select 1 or any other available number.
4.
Click the "Next" button to proceed with further configuration (else click "Cancel" to
discard the new configuration).
5.
In the "Select DataSet" window, select the radio button for "New DataSet" or "Existing
DataSet".
Report Properties
The report properties section can be viewed when any configured report is selected.
All the available parameters of the Report control block are displayed when clicking
"Report Advanced Configuration". Respective OptFields, TrgOps can be configured by
either selecting "True" or "False". Buffer time is given in milliseconds.
Configure Dataset Items
1.
Select the required logical node under IED name> LD name relay "tree".
2.
Go to the required dataset item.
3.
Drag and drop the item to the "DataSet Elements" section.
Maximum Report Control Blocks
The 3 Series relay supports a maximum of 4 report control blocks. Buffered and unbuffered
reports are both included in the maximum. The user can configure reports based on the
Report Configurations Supported table as follows.
Table 4-2: Report Configurations Supported
Buffered Report
4
3
2
1
The GOOSE tabs in IEC61850 Configurator permits configuration of data set and GOOSE
control block for transmission and the subscription for the reception of gooses.
The use of this two tabs is described in the section
page 4-27.
CHAPTER 4: 3 SERIES IEC61850 GOOSE
Unbuffered Report
0
1
2
3
Using the IEC 61850 configurator
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Total Reports
4
4
4
4