IEC60870-5-104 PROTOCOL

IEC 60870-5-104 protocol settings

NOTE:
3-30
Select the Settings > Communications > IEC 60870-5-104 > Protocol menu item to open
the IEC 60870-5-104 protocol configuration window.
Settings
GENERAL
IEC 60870-5-104 Function
IEC TCP Port
IEC Common Address of ASDU
IEC Cyclic Data Period
IEC TCP Connection Timeout
Fault Report Mapping in DNP/104
CLIENT ADDRESS
Client Address 1*
Client Address 2*
Client Address 3*
Client Address 4*
Client Address 5*
The Client Address setpoints marked "*" are shared with DNP, as only one protocol can be
active at a time.
The 3 Series relay can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the 3
Series relay maintains two sets of IEC 60870-5-104 data change buffers, no more than two
masters should actively communicate with the 3 Series relay at one time. Five client
address settings are used to filter which master is suitable for communicating with 3 Series
relay.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC
60870-5-104 FUNCTION setting is set to "Enabled", the DNP protocol will not be
operational.
If IEC Cyclic Data Period is set to 0 there will be no cyclic data response.
Some other settings can be added to select the first address of the different Object
Information. These settings can be removed to be consistent with the UR but are very
useful for integrating the relay into a system.
Settings
Object Information Address Binary
Object Information Address Analog
Object Information Address Counters
Object Information Address Command
By default, the Object Information Address for the different data will be as follows:
M_SP (Single Points) = 1000
M_ME (Measured Value) = 2000
M_IT (Integrated Totals) = 3000
C_SC or C_DC (Single or Double Command) = 4000
Range
Disabled, Enabled
1 to 65535
0 to 65535
0 to 65535 s
10 to 300 s
Disabled, Enabled
Range
1 to 16777215
1 to 16777215
1 to 16777215
1 to 16777215
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 3: ETHERNET INTERFACE
Default
Disabled
2404
0
60 s
120 s
Disabled
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
Default
1000
2000
3000
4000